Сегодня в пол-второго ночи одновременно испортились оба блока питания PWR-2700-AC в шасси Cisco 7606.
При этом супервизор сказал "у меня нет живых блоков питания, питания недостаточно для линейных карт, гашу их все".

#show power 
system power redundancy mode = redundant
system power redundancy operationally = non-redundant
system power total =     0 Watt
system power used =       744.66 Watts (17.73 Amps @ 42V)
system power available = 0 Watt
                        Power-Capacity PS-Fan Output Oper
PS   Type               Watts   A @42V Status Status State
---- ------------------ ------- ------ ------ ------ -----
1    PWR-2700-AC        2669.10 63.55  -      -      off
2    PWR-2700-AC        2669.10 63.55  -      -      off
                        Pwr-Allocated  Oper
Fan  Type               Watts   A @42V State
---- ------------------ ------- ------ -----
1    FAN-MOD-6HS         180.18  4.29  OK
                        Pwr-Requested  Pwr-Allocated  Admin Oper
Slot Card-Type          Watts   A @42V Watts   A @42V State State
---- ------------------ ------- ------ ------- ------ ----- -----
1    WS-X6724-SFP        125.16  2.98     -     -     on    off (FRU-power denied)
2    WS-X6748-SFP        254.94  6.07     -     -     on    off (FRU-power denied)
3    WS-X6748-GE-TX      325.50  7.75     -     -     on    off (FRU-power denied)
4    WS-X6704-10GE       295.26  7.03     -     -     on    off (FRU-power denied)
5    WS-SUP720-3B        282.24  6.72   282.24  6.72  on    on
6    WS-X6748-GE-TX      325.50  7.75   282.24  6.72  on    off (FRU-power denied)

Каждый из блоков питания получал ввод от мощного источника бесперебойного питания, один от APC8000, второй от General Electric. После сбоя оба стали индицировать OUTPUT FAIL, супервизор перезагрузился, выдав на консоль:

*Mar  3 06:43:23: %OIR-SP-6-INSPS: Power supply inserted in slot 1
*Mar  3 06:43:23: %C6KPWR-SP-2-PSFAIL: power supply 1 output failed.
*Mar  3 06:43:23: %C6K_POWER-SP-4-GLITCH: Recovered from glitch in system power supply.
*Mar  3 06:43:23: %OIR-SP-6-INSPS: Power supply inserted in slot 2
*Mar  3 06:43:23: %C6KPWR-SP-2-PSFAIL: power supply 2 output failed.
*Mar  3 06:43:23: %C6K_POWER-SP-4-GLITCH: Recovered from glitch in system power supply.
*Mar  3 06:43:26: %C6KPWR-SP-4-UNDERPOWERED: insufficient power to operate all FRUs in system.
*Mar  3 06:43:26: %C6KPWR-SP-2-INSUFFICIENTPOWER: Powering down all linecards as there is not enough power to operate all critical cards
*Mar  3 13:43:28: %SNMP-5-COLDSTART: SNMP agent on host M-19 is undergoing a cold start
*Mar  3 06:43:26: %C6KENV-SP-4-FANHIOUTPUT: Version 2 high-output fan-tray is in effect
*Mar  3 06:43:26: %C6KPWR-SP-4-POWERDENIED: insufficient power, module in slot 1 power denied.
*Mar  3 06:43:26: %C6KPWR-SP-4-POWERDENIED: insufficient power, module in slot 2 power denied.
*Mar  3 06:43:26: %C6KPWR-SP-4-POWERDENIED: insufficient power, module in slot 3 power denied.
*Mar  3 06:43:26: %C6KPWR-SP-4-POWERDENIED: insufficient power, module in slot 4 power denied.
*Mar  3 06:43:26: %C6KPWR-SP-4-POWERDENIED: insufficient power, module in slot 6 power denied.


Поставили в шасси другой блок питания вместо сбойных и 7606 заработала. Полшестого утра, пойду посплю немного.

Date: 2014-03-05 10:20 (UTC)
From: [identity profile] click0.livejournal.com
Вывод?
Раз в 3 месяца планово тестировать железо.
Поочередное отключение питания к каждому БП - одно из них.

Предусмотреть резервирование N+1, а отдельных узлов и железок до N+2.